Open vented primary systems
The Greenstar FS CDi series is designed for connection to an open vented fully pumped heating and hot water system.
The following points are for guidance only. The system installation should be carried out in accordance with BS 5449:Part1.
The feed and expansion pipes must rise continuously from the appliance and must be of the minimum diameter shown below.
The cistern must be arranged to provide a minimum static head of 0.25 metres above the top of the highest point in the heating circuit.
Air in the appliance is expelled through the vent pipe or dissipated into the system. Manual air vents should be fitted at any high points in the system.