Compartment installation

The appliance may be installed in any room, although particular attention is drawn to the requirements of the IEE regulations applicable and in Scotland the electrical provisions with respect to installation in a room containing a bath or shower.

Air supply

  1. The room in which the appliance is installed does not require a purpose provided air vent.

  2. If the appliance is installed in a cupboard or compartment with dimensions that allow the following minimum clearances, then no ventilation is required:

Image of FS CDi compartment installation table

*This space can be reduced to 50mm for one side only as long as both the side clearances add up to the total of both the side measurements shown or more.

Image of FS CDi condensate clearances

*Space required for unvented areas with a removable door or panel.
**This space can be reduced to 50mm for one side only as long as both the side clearances add up to the total of both the side measurements shown or more.