[Skip to main content] [Skip to secondary navigation] [Skip to accesskey list ]

Compartment installation

The appliance may be installed in any room, although particular attention is drawn to the requirements of the IEE regulations applicable and in Scotland the electrical provisions with respect to installation in a room containing a bath or shower.

  1. The room in which the appliance is installed does not require a purpose provided air vent.

  2. If the appliance is installed in a cupboard or compartment with dimensions that allow the following minimum clearances, then no ventilation is required:

Image of Combi boiler compartment installation table

Ventilation free compartment installation - minimum clearances

Image of Compartment installation for i Junior and Si

Image of Compartment installation for CDi combi boilers

Social media


Home | Find a boiler | Head office contacts | Sitemap | Accessibility |