Sealed primary systems
The appliance is fitted with a manual reset high limit thermostat and is suitable for use with a sealed primary system.
The system should be installed in compliance with the requirements of BS 5449: Part1. The boiler must be fitted with a spring loaded safety valve set to operate at 3bar (45 psi) and the pipe connections made through the system must be capable of sustaining a pressure of up to 3bar.
Manual air vents should be fitted at any high points in the system.
The following is a list of major items which must be fitted to the system:
- Safety valve - 3bar
- Pressure gauge - 0-4bar
- Expansion vessel
- Automatic air vent

System filling and make-up
To comply with the Water Authority requirements, the system should be filled via a temporary hose connection to the mains cold water supply, with a double check valve assembly and test point fitted to the mains water side of a temporary circuit.
Valves and joints
It is very important that all valves and joints are able to sustain a working pressure of up to 3bar (45psi). Particular care should be exercised when fitting radiator valves and only those of high quality to BS 2767:10 should be used. All other valves and fittings should comply with BS 1010.
Loss of water pressure from a sealed system will require continuous recharging with fresh water and consequential introduction of air. Air is highly corrosive and will considerably reduce life expectancy of radiators, pumps etc. Plastic pipework.
Plastic pipework
The use of plastic pipework is acceptable. However, some plastics are permeable to oxygen and must be avoided. Only pipework with a polymeric barrier should be used. Please note that the first 600mm of pipework connected to the boiler must be of copper or steel.


Social media