Compartment installation
Compartment clearances
Follow the requirements of BS5410 and note:
Minimum clearances must be maintained.
An access door is required to install, service and maintain the boiler and any ancillary equipment, i.e. condensate trap.
If fitting the boiler into an airing cupboard use a non-combustible material (if perforated, maximum hole sizes of 13mm) to separate the boiler from the airing space.
Compartment ventilation
Ventilation must be provided for boilers fitted into compartments as described in BS5410.
A minimum of 2 air vents must be fitted, one at low level (C) and another at high level (D) onto the same wall using the same air (E) for circulation.
Free air must not be taken from a room or internal space containing a bath or shower and must not communicate with a protected area such as a hall, stairway, landing, corridor, lobby, shaft, etc.
Air vents must allow access for clean free air and must be sited to comply with the flue terminal position requirements.
Air ducting runs must not exceed 3m.
Low level air vents must be less than 450mm from the floor.
A warning label must be added to the vents with a statement to the effect: “Do not block this vent. Do not use for storage”.

A Compartment
B Boiler
C Low level vent
D High level vent
E Air supply
Conventional flue

Room sealed flue

*Internal air to and from a space/room inside the building.
**External air to and from directly outside the building.