Fully pumped sealed primary systems

Fully pumped sealed primary system

  • A pressure relief valve (P) (spring loaded safety valve set to operate at 3bar) must be fitted to the heating flow pipe as close as possible to the boiler.

  • An expansion vessel (B) should be fitted to the heating return pipe close to the boiler and pressurised for the system volume according to the instructions supplied with the vessel.

  • A pressure gauge (G) (3bar min.) must be fitted to the heating flow pipe.

  • An automatic vent (N) must be fitted.

Image of Fully pumped sealed primary systems