[Skip to main content] [Skip to secondary navigation] [Skip to accesskey list ]

Compartment installation

Compartment clearances

Follow the requirements of BS5410 and note:

  • Minimum clearances must be maintained.
  • An access door is required to install, service and maintain the boiler and any ancillary equipment.
  • If fitting the boiler into an airing cupboard use a non-combustible, perforated material (maximum hole sizes of 13mm) to separate the boiler from the airing space.

Venting compartments

  • Ventilation must be provided for boilers fitted into compartments as described in BS5410.
  • A minimum of 2 air vents must be fitted, one at low level (C) and another at high level (D) onto the same wall using the same air (E) for circulation.
  • Free air must not be taken from a room or internal space containing a bath or shower and must not communicate with a protected area such as a hall, stairway, landing, corridor, lobby, shaft etc.
  • Air vents must allow access for clean free air and must be sited to comply with the flue terminal position requirements.
  • Air ducting runs must not exceed 3m.
  • Low level air vents must be less than 450mm from the floor.
  • A warning label must be added to the vents with a statement to the effect: “Do not block this vent. Do not use for storage”.

Compartment installation

Air supply - CF (conventional flue)

An adequate supply of free air must be delivered to the boiler for combustion purposes through a permanent inlet, such as an air brick, into the area where the boiler is situated.

Image of air supply

*Due to changes in BS 5410 and modern building design these figures no longer incorporate the adventitious ventilation allowance.

Conventional flue

Compartment installation

Room sealed flue

Compartment installation

Social media


Home | Find a boiler | Head office contacts | Sitemap | Accessibility |