Compartment installation
Compartment clearances (kitchen models)
Follow the requirements of BS5410 and note:
- Minimum clearances must be maintained.
- An access door is required to install, service and maintain the boiler and any ancillary equipment.
- If fitting the boiler into an airing cupboard use a non-combustible material (if perforated, maximum hole sizes of 13mm) to separate the boiler from the airing space.
Compartment ventilation
- Ventilation must be provided for boilers fitted into compartments as described in BS5410.
- A minimum of 2 air vents must be fitted, one at low level (C) and another at high level (D) onto the same wall using the same air (E) for circulation.
- Air vents must allow access for clean free air and must be sited to comply with the flue terminal position requirements.
- Air ducting runs must not exceed 3 metres.
- Low level air vents must be less than 450mm from the floor.
- A warning label must be added to the vents with a statement to the effect: “Do not block this vent. Do not use for storage”.