Supply requirements

The heat pump should be connected to 230V single phase electricity supply and wired directly into a consumer unit protected by an appropriate D characteristic miniature circuit breaker according to the table shown.

Starting current (A)
6kW heat pump 7kW heat pump 9kW heat pump 11kW heat pump
22.9 23.8 30.9 34.6


Recommended fuse according to electrical output* (AaM)
6kW electric heater
6kW heat pump 7kW heat pump 9kW heat pump 11kW heat pump
40 40 50 50
9kW electric heater
6kW heat pump 7kW heat pump 9kW heat pump 11kW heat pump
50 63 63 63