Greenskies Solar-Lito installation guide

Greenskies Solar-Lito panel installation guide

Panel dimensions and clearances

Image of Greenskies Solar-Lito panel dimensions and clearances


Make sure you have the following clearance space to install the equipment.

Dimension A and B
Surface area required for collectors.

Dimension C
At least two free rows of tiles to roof peak or chimney. Especially in the case of wet tiles, there is risk of damaging the roof*.

Dimension D
Prominence of the roof, including the thickness of the façade of the building.

Dimension E
At least 30cm should be cleared for the installation of the connection cables in the attic below.

Dimension F
At least 40cm for the installation of the connection cables in the attic, above (when installing the retainer, make sure that there is sufficient space in the water outlet area.

Dimension G
At least 50cm on the left and on the right of the collector array for the connection cables under the roof.

Dimension H
Dimension H corresponds to 1,900mm (2m2 collectors) or 900mm (1m2 collectors), and is the minimum distance from the upper corner of the collector until the middle of the lower rail, which is fixed first.

*Please note: No in-roof option is available on this range.

Required distance for vertical collectors

Number of collectors Dimension A Dimension B
1 1,095m 1,032m(1) 2,026m(2)
2 2,196mm
3 3,296m
4 4,397m
5 5,497m
6 6,598m
7 7,698m
8 8,799m
9 9,899m
10 10,000m