Why is the pump running constantly on a Greenstar CDi boiler?
The pumps on the Greenstar CDi range have a permanent live feed to them. If the pump is always running, there are generally 3 causes for this:
- The speed control wire (purple, white and black) going to the pump is damaged - check continuity and connection.
- The boiler has a weather compensating controller fitted (FW100 or Wave smart internet connected controller). The pump will run constantly to monitor the flow temperature and maintain heat curve.
- The PCB is faulty and telling the pump to run when it should not be running.
More All FAQs
- The MyWorcester App has now been retired and is no longer available, please download our new app.
- How many colours is the EasyControl available in?
- How are installers selected to complete FastTrack installation jobs?
- What happens if the customer doesn’t meet the FastTrack criteria?
- How do I give my engineers access?
- Top tips commissioning a Greenstar Danesmoor oil boiler
- Is an external air break required when a condensate pipe is terminated into a rainwater downspout?
- How do I re-route a condensate pipe to reduce the external run?
- Have you got more information on how to wire controls to your range of Greenstar gas boilers?
- How many immersion heaters do you have in your cylinders?